19
MAINTENANCE
D
isplay
M
essage
Action Comment
OK None Normal operating mode
Initial None Program is Initializing, level reading held at 4 mA set point. This is a
t
ransient condition.
NoSignal No level signal being detected. Make sure float is not damaged and within measuring range.
Hi Temp Present temperature in
electronics compartment is
a
bove +80° C
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter
Lo Temp Present temperature in
electronics compartment is
b
elow -40° C.
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter
TrimReqd Factory set Loop values are
defaults, loop output may be
inaccurate
Consult factory
Cal Reqd Factory set default calibration
parameters are in use, level
reading may be inaccurate
Consult factory
LoopFail Loop current differs from
expected value
Consult factory
Note: In case of loop failure, error signal will follow the failing trend;
meaning the unit will show 3.6 mA when the reviewed loop current by
the device is found too low. The unit will show 22 mA in case the
reviewed loop current is found too high.
DfltParm Internal non-volatile parameters
have been defaulted
Consult factory
Float 2
Fail
No level signal detected from
float 2
Make sure 2 floats are being used, are not damaged, and within
measuring range
Float 1
Fail
No level signal detected from
float 1
Make sure float is not damaged, and within measuring range
Snsr Brd Measurement board not
responding
Consult factory
ERROR MESSAGES
PACTware
™
PC Program
The JUPITER
®
200 series of
fer the ability to do Trending and Waveform analysis using a PACTware DTM. This is a power-
ful troubleshooting tool that can aid in the resolution of some of the Error Messages shown above.
Refer to Bulletins 59-101 and 59-601 for more information.