7
MENU: STEP BY STEP PROCEDURE – Jupiter 200: Level only
S
creen Action Comment
Diagnostics
1
9
2
1
2
2
23
2
4
Trim Lvl
xx.xx
New Pass
xxx
20
F1 Cnts
xxxx
Language
(select)
JupiterHT
Ver 3.0A
DispFact
(select)
14
1
5
1
6
1
7
18
Trim 4
xxxx
Trim 20
xxxx
Loop Tst
xx.x mA
Deadband
xx.x
Snsr Mnt
(select)
F
ine tune the 4 mA point.
A
ttach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
E
nter a mA output value.
S
et mA Output to any given value to perform loop test.
N
one, do not adjust.
F
actory setting.
Select the type of mounting. «MLI Top» External mount Jupiter – Top mounted Jupiter
«
M
LI Bot
»
External mount Jupiter – Bottom mounted Jupiter
«
Dir Near» Direct mount Jupiter – NPT, BSP and
Flanged ≤ 600 lbs / PN160
«D
ir Ext
»
Direct mount Jupiter – Flanged ≥ 900 lbs / PN250
Enter value
t
o adjust level reading.
Allows to compensate for a fixed level deviation.
Diagnostic display. Shows time of flight from the start pulse to reflected signal from level.
Enter new password. Use arrows to select desired value. Values between 0 and 255.
Select language Select «English» or «Espagnol».
N
one, do not adjust.
F
actory setting. «
V
er
»
refers to software version.
Advanced diagnostics. See page 14.
Komentarze do niniejszej Instrukcji